InteliDrive DCU Industrial 3.4.0 Global Guide
129
Setpoint group
Engine protect
Related FW
3.4.0
Range [units]
0 .. 60 [s]
Default value
0
Force value Alternative
config
Step
1
Comm object
10571
Related applications
AS, SS
Description
Delay for Force block protection activation after binary input Force Block 3 is opened. Protection
deactivation is without delay. Protection is activated/deactivated independent on engine running or not
running state.
ForceBlockDel3
Setpoint group
Engine protect
Related FW
3.4.0
Range [units]
0 .. 200 [%]
Default value
110
Force value
Alternative config
Step
1 % of
Comm object
8263
Related applications
AS, SS
Description
Threshold for engine overspeed protection.
Overspeed
Setpoint group
Engine protect
Related FW
3.4.0
Range [units]
0 ..
[RPM]
Default value
30
Force value
Alternative config
Step
1
Comm object
8260
Related applications
AS, SS
Description
Underspeed alarm is activated when engine is running and actual RPM is below the UnderSpeed threshold.
UnderSpeed
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...