RPMdep protect (AS only)
RPM dependent Oil pressure and Coolant pressure protections are available in AS (propulsion) application only.
Both protections are by default set to Protection block type = RunOnlyBlkDel1 (Engine running - block delay 1).
There are two setpoints for linear Warning limit, two for Shutdown limit and one for delay. Setpoints adjusting
step and range depends on corresponding sensor characteristics.
Note:
The particular RPM dependent protection is fully disabled if both xxxIdlexxx and xxxNomxxx parameters
are set to value 0,0. I.e. the protection is not activated even if measured value is negative (e.g. when there is a
wrong sensor calibration).
Setpoint group
RPMdep protection (AS
only)
Related FW
3.4.0
Range [units]
0.0 .. 10.0 [Bar]
Default value
0.0
Force value
Alternative config
Step
0.1
Comm object
10140
Related applications
AS
Description
Linear Warning characteristic is defined by two points for
and
. OPIdleRPMWrn defines oil pressure warning level at idle speed.
OPIdleRPMWrn