InteliDrive DCU Industrial 3.4.0 Global Guide
296
Terminator
Cold Junction Compensation (CJC) settings
Please have a look at Cold junction compensation in
Cold Junction Compensation (CJC) (page 323)
chapter.
Technical data
Dimension (W × H × D)
110 × 110 × 46 mm (4.3” × 4.3” × 1.8”)
Weight
237.5 grams
Interface to controller
CAN1
Analog inputs (not electric separated)
8, no galvanic separated
Measuring
±100 mV
Accuracy
± 0.1 % of actual value + ± 100 µV (± 3 °C)
Internal sensor for measuring cold junction - Accuracy
±1 °C in temperature range -20 °C ÷ +70 °C
Galvanic separation
CANbus is galvanic separated from the
measurement and power supply.
All analog inputs are galvanic separated from
power supply.
Analog inputs are not galvanic separated
between channels
Power supply
8 to 36 V DC
Protection
IP20
Current consumption
35 mA at 24 V ÷ 100 mA at 8 V
Storage temperature
- 40 °C to + 80 °C
Operating temperature
- 30 °C to + 70 °C
Heat radiation
2 W
Thermocouples galvanically separated and galvanically non-separated are supported.