InteliDrive DCU Industrial 3.4.0 Global Guide
313
Analog outputs
1 channel AOUT1. Type of output:
0-10V DC
0-20mA
PWM (5V, freq 2,4Hz ÷2,4kHz)
Analog output has 4-pins connector – GND and one pin for each type of output.
All analog inputs can be configured to any logical function or protection.
It is possible to connect up to 5 modules to the InteliGen-NT, InteliSys-NT or InteliMains-NT controllers.
In case of connection Inteli AIO9/1 module to ID-DCU controller – number of module depends on using fw.
Inteli AIO9/1 module is designed for connecting to controller CAN1 bus.
Supported sensors
Sensors
User curves
PT1000 [°C] (fix)
NI1000 [°C] (fix)
0-2400Ω (fix linear)
± 65 V DC (fix linear)
+-75mV (fix linear)
Thermocpl J [°C] (fix)
Thermocpl K [°C] (fix)
Thermocpl L [°C] (fix)
Thermocpl (nc) J [°C] (fix)
Thermocpl (nc) K [°C] (fix)
Thermocpl (nc) L [°C] (fix)
Thermocpl (nc) J [°F] (fix)
Thermocpl (nc) K [°F] (fix)
Thermocpl (nc) L [°F] (fix)