InteliDrive DCU Industrial 3.4.0 Global Guide
157
Setpoint group
DetCon20
Related FW
3.4.0
Range [units]
0 .. 255 [-]
Default value
40
Force value
Alternative config
Step
1
Comm object
10304
Related applications
AS, SS
Description
Immediate stop limit is knocking value above which DetCon20 binary output TRIP is activated. This causes
engine to shut down if properly wired.
ImmStopLimit
Setpoint group
DetCon20
Related FW
3.4.0
Range [units]
0.0 .. 100.0 [%/s]
Default value
30.0 %/s
Force value
Alternative config
Step
0.1 %/s
Comm object
10300
Related applications
AS, SS
Description
Decrease ramp specifies rate at which is the timing reduction signal (analog output) decreased as soon as
knocking drops below the
(ignition reduction limit).
DecreaseRamp
Setpoint group
DetCon20
Related FW
3.4.0
Range [units]
0.0 .. 100.0 [%]
Default value
40.0 %
Force value
Alternative config
Step
0.1 %
Comm object
10301
Related applications
AS, SS
Description
Timing reduction gain influences rate at which timing reduction signal (analog output) is amplified when
knocking is detected.
TimingRedGain
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...