8.2.10 I-CB Communication bridge
Image 8.16 Dimensions of I-CB
All dimensions are in mm.
I-CB unit can be mounted on DIN rail (35 mm).
I-CB (Communication bridge) is CAN bus interface between Controller and Engine Control Unit (ECU)
that has not standard J1939 communication (MTU, CAT etc.). Engine values (RPM, Oil pressure and
other) are received from ECU via CAN and corresponding sensors are not needed on controller. Use
ICBEdit software for I-CB configuration (included in installation package).
I-CB wiring and configuration
1. Configure I-CB using I-CBEdit software. Configured I-CB behaves like fictive IS-AIN and IS-BIN units. I-CB
configuration associates selected values (from ECU database) received from Engine Control Unit to
selected CAN addressees (fictive IS-AIN, IS-BIN inputs and outputs).
2. Configure corresponding controller CAN addresses and tick in PC configuration tool.
3. Configure separate inputs and outputs in corresponding Analog, Binary inputs, outputs in PC configuration
tool.