InteliDrive DCU Industrial 3.4.0 Global Guide
241
Related FW
3.4.0
Related applications
AS, SS
Comm object
182
Description
There are two Statistics registers Memo1 and Memo2. Those statistic values are based on Logical Analog
Input Memory1 or Memory2 value in the time of Logical Binary input Memo1 Trigger or Memo2 Trigger rising
edge. Both statistics values is possible to modify in InteliMonitor – Set Statistics command.
Memory2
Related FW
3.4.0
Related applications
AS, SS
Comm object
56
Description
If there is an additional terminal board between a thermocouple sensor and the IS-AIN8 (TC) module and
there is a significant temperature difference between this terminal board and the module, it is necessary to
measure the temperature at this terminal board and use this temperature for the thermocouple compensation
instead of the internal temperature of the module.
Cold Temp 1
Logical Analog input is intended for measurement of this thermocouple compensation
temperature for the IS-AIN8 (TC) module with index #1,
Cold Temp 2
corresponds to IS-AIN8 (TC) module
with index #2 etc.
Note:
Thermocouples without internal compensation "Thermo(nc)..." must be used for this case.
Cold Temp 1
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...