InteliDrive DCU Industrial 3.4.0 Global Guide
50
0-10 V
Y
Y
0-100 mV
Y
Y
PT100 [°F]
Y
Y
Y
PT1000 [°F]
Y
Y
Y
NI100 [°F]
Y
Y
Y
NI1000 [°F]
Y
Y
Y
Thermocpl J [°F]
Y
Y
Y
Y
Thermocpl K [°F]
Y
Y
Y
Y
Thermocpl L [°F]
Y
Y
Y
Y
Tristate
Thermo(nc) J [°C]
Y
Y
Y
Y
Thermo(nc) K [°C]
Y
Y
Y
Y
Thermo(nc) L [°C]
Y
Y
Y
Y
Thermo(nc) J [°F]
Y
Y
Y
Y
Thermo(nc) K [°F]
Y
Y
Y
Y
Thermo(nc) L [°F]
Y
Y
Y
Y
0-5 V
Y
0-10 kΩ
Y
±65 V
Y
±75 mV
Y
Note:
* IGS-PTM has hardware range 0-20mA but offered sensor in DriveConfig is ±20 mA
** IGS-PTM has hardware range 0-250 Ω only - DriveConfig offers correct sensor for I/O configuration but for
User define input curve only sensor 0-2400 Ω.
IGS-PTM
0-100 mV, 0-2400 Ω, ±20 mA
IS-AIN8
0-100 mV; 0-2400 Ω; 0-2.4 V; 0-10V; ±20 mA; 0-20 mA passive, 4-20 mA
active; 4-20 mA passive
I-AIN8
0-2.4 V; 0-10 V; 0-2400 Ω; ±20 mA;0-20 mA passive, 0-10 kΩ; 0-5 V; 4-20 mA
active; 4-20 mA passive
I-IS-AIN8TC
none
I-AIO9
0-2k4Ω; ±65 V; ±75 V
User curves range
Note:
Fahrenheit sensors are supported from IS-AIN8 of sw version 2.2 only.
Note:
Controller user curves ("CU 'sensor range' ") are not possible to use for external extensions, it is
necessary to configure standard user curve (= without "CU" on the beginning of the name of the user curve
range).
4.3.6 Binary inputs/outputs on ID-DCU Industrial
Use wiring cables min. of 1.0 mm2 to ensure proper function.
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...