InteliDrive DCU Industrial 3.4.0 Global Guide
200
Related FW
3.4.0
Related applications
AS, SS
Comm object
37
Description
Ignition system activation / deactivation during start - stop procedure.
The output becomes active during cranking if RPM > 30, becomes inactive during cranking pause and after
stop of the engine (RPM = 0).
Ignition
Related FW
3.4.0
Related applications
AS, SS
Comm object
264
Description
1 sec (fix) pulse prior to transfer from
to
state.
Unload
Related FW
3.4.0
Related applications
AS, SS
Comm object
74
Description
Closes in cooling state, opens after engine stop.
Cooling
Related FW
3.4.0
Related applications
AS, SS
Comm object
22
Description
Closed output opens the fuel solenoid. Adjustable to DIESEL or GAS. See also the
setpoint description.
Fuel Solenoid
Related FW
3.4.0
Related applications
AS, SS
Comm object
40
Description
The output closes when engine starts and opens
delayed after stop the engine.
Cooling Pump
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...