InteliDrive DCU Industrial 3.4.0 Global Guide
280
Analog output (values) configuration
Any of values from the Source list can be configured to any physical or ECU / J1939 (virtual) Analog output.
Module
Number of outputs
Note
ID-SCM
3
10 V or 20 mA or 10 V / 10 kΩ
IGS-PTM
1
10 V or 20 mA
I-AOUT8
8
10 V or 20 mA or pwm
I-IO8/8
2
20 mA (10 V or pwm not supported by ID-DCU Marine 2.2)
ECU (J1939)
4 (virtual)
Format depends on ECU
Analog outputs availability
Analog output configuration
It is possible to convert Source analog value by linear interpolation (conversion). The conversion is given by
definition of two points, Low and High one.
Following is example of transfer characteristics 0 – 100 % to 0 – 20 mA.
Following are examples of transfer characteristics 0 – 100 % to 4 – 20 mA. The first case is transfer
characteristics -25 – 100 % to 0 – 20 mA, it contains the needed conversion to 4 – 20 mA.
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...