InteliDrive DCU Industrial 3.4.0 Global Guide
54
4.3.10 ID-DCU Industrial Analog inputs software configuration
Note:
ID-DCU Industrial hardware jumper must correspond with software configuration.
Configuration
See drawing above
Property
Value
Name
Value name is displayed on the screens and in the Alarm list and History record.
Enter up to 14 ASCII characters.
Name is automatically set to Function name if function is selected from the Logical function
list see Function item.
Dim
Dimension is displayed on the screens. Select dimension from the list or add a new one.
Sensor
Select sensor from the list or create a customer sensor characteristics in User sensor
window. There must be corresponding analog input hardware jumper setting in InteliDrive
controller. See Sensor availability in table below.
Resolution
Output value (reading) resolution. DriveConfig indicates when Resolution is out of the value
range.
Sensor
range
Full output value (reading) range for 20 mA (current), 250 Ω, 2400 Ω (resistive), 1 V, 4V, 5V,
100 mV (voltage) sensor.
Protection
Select from the list. Configure two protection levels as standard or more levels (window)
protection in Expert mode.
Active
when
Configure direction Over or Under limit when protection is activated. Options "Under
limit+Fls" and "Over limit+Fls" means that the protection is activated in case of Analog Input
value is Under/Over the protection limit or in case that non valid value (####) is indicated on
the Analog Input. More details in
Block type
Configure protection activity: All the time or Engine running with three different adjustable
delays when protectioln is active after engine start (RPM > Starting RPM).
Bargraph
0%
Bargraph starting value.
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...