InteliDrive DCU Industrial 3.4.0 Global Guide
177
Related FW
3.4.0
Related applications
AS, SS
Comm object
41
Description
Skips Idle Time and switch controller from Idle to Running state when closed before Idle Time is over.
Nominal Speed
Related FW
3.4.0
Related applications
SS
Comm object
162
Description
Binary input function for loaded engine indication.
Loaded
Related FW
3.4.0
Related applications
AS
Comm object
163
Description
Binary input activates Engine start via clutch. Engine is started by the other running engine via closed clutch
- binary output
Clutch Connect
. See
protection setpoint.
EnClutchStart
Related FW
3.4.0
Related applications
AS, SS
Comm object
44
Description
Blocks all protections except
, Emergency Stop and protections configured as “Sd
override” (=Sprinkler).
All alarms are detected
Alarms are recorded on the controller Alarm list screen
Alarm are recorded into History
Enabled Active calls remains active
Controller front panel engine RED LED blinks or lights
Note:
The setpoint Crank Attempts is not followed if Sd Override is active, crank attempts number is
then unlimited in case of Blackout Start.
Sd Override
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...