InteliDrive DCU Industrial 3.4.0 Global Guide
141
Setpoint group
Load sharing
Related FW
3.4.0
Range [units]
0.0 .. 100.0 [%]
Default value
50.0
Force value Alternative
config
Step
0.1
Comm object
10524
Related applications
AS
Description
See
Load sharing block diagram (page 144)
- the setpoint value is used instead of
in loadsharing state, if
is active and
reading via analog input is out of range (sensor fail is detected).
Back Up Speed3
Setpoint group
Load sharing
Related FW
3.4.0
Range [units]
0 .. 600 [s]
Default value
60
Force value
Alternative config
Step
1
Comm object
10102
Related applications
AS
Description
Engine clutch start protection. Start fail alarm is activated, if engine running condition is not detected during
MaxClStrPer delay time after
is closed.
MaxClStrtPer