InteliDrive DCU Industrial 3.4.0 Global Guide
126
Setpoint group
Engine protect
Related FW
3.4.0
Range [units]
0 .. 60 [s]
Default value
1
Force value
Alternative config
Step
1
Comm object
10131
Related applications
AS, SS
Description
Binary input protection is activated when input is closed for longer time than BinInp delay 1. To use this filter,
binary input protection Delay must be configured in DriveConfig to BinInp delay 1. For details see
description.
BinInp Delay 1
Setpoint group
Engine protect
Related FW
3.4.0
Range [units]
0 .. 60 [s]
Default value
5
Force value
Alternative config
Step
1
Comm object
10132
Related applications
AS, SS
Description
Binary input protection is activated when input is closed for longer time than BinInp delay 2. To use this filter,
binary input protection Delay must be configured in DriveConfig to BinInp delay 2. For details see
description.
BinInp Delay 2