InteliDrive DCU Industrial 3.4.0 Global Guide
333
BINARY OUTPUT
8 binary output
CAN
CAN1 line
RS232-TTL
Interface for programming
POWER
Power supply
BINARY INPUTS
8 LEDs for binary input indication
BINARY OUTPUT
8 LEDs for binary output indication
Tx, Rx
Indication transmitted or received data
POWER
Power supply LED indication
CAN_R
Terminating CAN resistor
RUI
Analog inputs configuration
RESET
Programming / reset
BOOT
Programming
IGS
Controller type selection
AIN BLOCK
Block of all Analog inputs
STOP
Service jumper
ADR1
Module’s address settings
ADR2
Compensation button
Long wires resistance compensation
Note:
Configuration jumpers IGS, ADR1, ADR2 are OPEN by default.
CAN_R jumper is CLOSE by default (IG-IOM mode).
Analog inputs are configured for resistance measurement by default.
Address and jumpers setting
Controller type selection
The type of controller to be used with IGS-PTM must be selected via jumper labeled IGS accessible at the lower
PCB.
IGS jumper
Controller type
OPEN
IL-NT, IC-NT, ID (FLX)
CLOSE
IG-NT, IS-NT, IM-NT, ID-DCU, ID-Mobile, IL
Table 8.10 IGS jumper description
Address configuration
If IGS-NT controller type is selected (by IGS jumper), address of IGS-PTM could be modified via jumpers
labeled ADR1 and ADR2.
ADR1
ADR2
BIN module
BOUT module
AOUT module
AIN module
Open
Open
1
1
1
1
Close
Open
2
2
2
2
Open
Close
3
3
3
3
Close
Close
4
4
4
4
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...