InteliDrive DCU Industrial 3.4.0 Global Guide
132
Setpoint group
Engine protect
Related FW
3.4.0
Range [units]
0 .. 65535 [h]
Default value
65535
Force value
Alternative config
Step
1
Comm object
9648
Related applications
AS, SS
Description
Running hours count down counter is decremented when engine is running. Service alarm is indicated in
Alarm list and History record is done when counter reaches zero. Service time setpoint is initial counter
value and it is gradually decrement when engine runs.
Note:
Once the service time has elapsed the Service time will have to be adjusted to non-zero value to
clear the alarm and begin a new countdown.
Service Time
Setpoint group
Engine protect
Related FW
3.4.0
Range [units]
[DEFAULT, ALARM ONLY]
Default value
DEFAULT
Force value
Alternative config
Step
[-]
Comm object
15813
Related applications
AS, SS
Description
DEFAULT:
is activated , if ECU alarm is received by controller.
ALARM ONLY:
is not activated, if ECU alarm is received by controller.
ECUAlarmMode