InteliDrive DCU Industrial 3.4.0 Global Guide
130
Setpoint group
Engine protect
Related FW
3.4.0
Range [units]
0 .. Nominal RPM [RPM]
Default value
500
Force value
Alternative config
Step
1
Comm object
10139
Related applications
AS, SS
Description
Binary output Ready to load is closed if RPM > MinLoadSpeed and engine is in Running state. Use this
output to enable/disable connecting of engine load. MinLoadSpeed is a condition to close
when panel I/0 button is used to connect load to engine.
MinLoadSpeed
Setpoint group
Engine protect
Related FW
3.4.0
Range [units]
Batt <V.. 40.0 [V]
Default value
30.0
Force value
Alternative config
Step
0.1
Comm object
9587
Related applications
AS, SS
Description
Warning level for battery over voltage.
Batt > V
Setpoint group
Engine protect
Related FW
3.4.0
Range [units]
8.0 .. Batt >V [V]
Default value
8.0
Force value
Alternative config
Step
0.1
Comm object
8387
Related applications
AS, SS
Description
Warning level for low battery voltage.
Batt < V