InteliDrive DCU Industrial 3.4.0 Global Guide
55
Bargraph
100%
Bargraph ending value.
Function
Select from the list if function is required or leave free if input is a protection only.
Offset
Measured value offset.
Note:
Some configuration items (e.g. Protection) stay without change when Property - Sensor is changed to
None.
Sensors availability
Sensors available on ID-DCU Industrial
AI1 - AI4
Resolution
Sensor range
HW jumper
Pt1000/°C, Ni1000/°C,
Pt1000/°F, Ni1000/°F
Fix, not configurable
Resistance: 3-4
4-20 mA active,
±20 mA active (me only)
Adjustable -
see Hint
below.
For 20 mA input
Current: 1-2
0-250 Ω, 0-2400 Ω
For 250 or 2400 Ω
Input
Resistance: 3-4
Tristate
Resistance: 3-4
0 to 4 VDC
Adjustable
Voltage: 2-3
Sensors available on ID-DCU Industrial
AI5 - AI8
Resolution
Sensor range
HW jumper
Pt100/°C, Pt1000/°C, Ni100/°C, Ni1000/°C,
Pt100/°F, Pt1000/°F, Ni100/°F, Ni1000/°F
Fix, not configurable
Resistance: 3-4
Thermocpl J/°C, Th K/°C, Th/°C,
Thermocpl J/°F, Th. K/°F, ThL/°F
Fix, not configurable
Voltage: 2-3
4-20 mA active, ±20 mA active
Adjustable -
see Hint below.
For 20 mA input
Current: 1-2
0-250 Ω, 0-2400 Ω
For 250 or 2400 Ω
input
Resistance: 3-4
±1 V, 0-100 mV
For 1V or 100mV
Voltage: 2-3
Tristate
Resistance: 3-4
0 to 5 VDC
Adjustable
Voltage: 2-3
Configuration examples
Conversion from 4-20 mA to 6.0 Bar Oil pressure sensor (Wrn+Sd protection and Oil press function)
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...