InteliDrive DCU Industrial 3.4.0 Global Guide
334
Table 8.11 CAN address settings
Analog inputs hardware configuration
Analog inputs can be configured for:
Resistance measurement
Current measurement
Voltage measurement
The type of analog inputs is configured via jumpers RUI located on lower PCB.
RUI
Analog input configuration
1 - 2
Resistance measuring
2 - 3
Current measuring
NO jumper
Voltage measuring
Table 8.12 Analog input settings
Programming firmware
Firmware upgrade is via AT-link (TTL). For programming is necessary to close jumper BOOT. RESET jumper is
used to reset the device. Close jumper to reset the device. For programming is used FlashProg PC tool.
LED indication
Binary inputs
Each binary input has LED which indicates input signal. LED is shining when input signal is set, and LED is
dark while input signal has other state.
Binary output
Binary output LED shining when binary output is set.
Power
LED status
Description
Dark
No required power connected
One flash and pause
Compensation fail
Three flashes and
pause
Compensation successful
Flashing
there is no communication between IGS-PTM and the controller.
Fast flashing
Detection of CAN communication speed
Lights
Power supply is in the range and communication between IGS-PTM and controller
properly works.
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...