InteliDrive DCU Industrial 3.4.0 Global Guide
173
Related FW
3.4.0
Related applications
AS
Comm object
158
Description
External “edge sensitive” request for engine start. Input is inactive in LOC (Local) mode. Adjustable number
of attempts (see setpoints
and
).
Remote Start
Blackout Start
RemRepStart
Panel START button
Input sensitive
Edge
sensitive;
2nd edge
skips Idle
Edge sensitive;
Edge sensitive;
Edge sensitive;
2nd edge skips Idle
Active in MODE
SS; AS
SS
AS
SS; AS
LOC
Inactive in MODE
LOC
LOC
LOC
all time active
Number of starting
attempts
1 x
Engine params:
Crank Attempts
Engine
params:
Crank
Attempts
1 x
Engine starting signals
Remote Stop
Panel STOP button
(1 sec holding time for Stop button activation!)
Input sensitive
Edge sensitive;
2nd edge skips Cooling
Edge sensitive;
2nd edge skips Cooling
Active in MODE
SS; AS
SS; AS
Inactive in MODE
LOC
-
Engine stopping signals
Note:
is not followed if Sd Override is active, crank attempts number is
then unlimited in case of Blackout/RemRep Start.
Blackout Start / RemRepStart
Related FW
3.4.0
Related applications
AS
Comm object
159
Description
If input is active and Logical Analog input Requested RPM is not valid (out of range, sensor fail),
is set to
value.
= 0.0 %
when analog request is out of range and Binary input Back Up Speed is not active.
Back Up Speed1
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...