InteliDrive DCU Industrial 3.4.0 Global Guide
125
Setpoint group
Engine protect
Related FW
3.4.0
Range [units]
0 .. 60 [s]
Default value
30
Force value Alternative
config
Step
1
Comm object
10025
Related applications
AS, SS
Description
This parameter adjusts delay after engine start when alarms configured as RunOnlyBlkDel3 (i.e. "running
only", group #3) are started to be evaluated. The "running only" alarms are not beeing evaluated while the
engine is not running or then, after start, while the adjusted delay is running.
Note:
Engine running state =
RPM >
or
Analog input Oil Press >
or
Analog input Coolant Press >
(PRP only) or
Active Binary input RunIndication1 or
Active Binary input RunIndication2 or
Active Binary input RunIndication3.
RunOnlyBlkDel3