InteliDrive DCU Industrial 3.4.0 Global Guide
191
Related FW
3.4.0
Related applications
AS, SS
Comm object
2
Description
The output is closed if there is a communication failure with the RS485 interface.
The timeout for communication failure is 5 seconds.
Note:
When communication with any terminal is lost, the LBO:
is closed and a history
record is written. This history record can be enabled / disabled by the setpoint
AccessLockCOM2
Related FW
3.4.0
Related applications
AS, SS
Comm object
2
Description
The output is closed if there is a communication failure with CAN2 with address #1.
The timeout for communication failure of CAN2 interface is adjusted by the setpoint
.
Note:
When communication with any terminal is lost, the LBO:
is closed and a history
record is written. This history record can be enabled / disabled by the setpoint
AcsLockCAN2(1)
Related FW
3.4.0
Related applications
AS, SS
Comm object
2
Description
The output is closed if there is a communication failure with CAN2 with address #2.
The timeout for communication failure of CAN2 interface is adjusted by the setpoint
.
Note:
When communication with any terminal is lost, the LBO:
is closed and a history
record is written. This history record can be enabled / disabled by the setpoint
AcsLockCAN2(2)
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...