InteliDrive DCU Industrial 3.4.0 Global Guide
340
8.2.11 I-AOUT8
Description
I-AOUT8 is an extension unit with 8 analog outputs. Each analog output can be switched to
0 to 20 mA DC
0 to 10 V DC
PWM (Pulse With Modulation on 1.2 kHz)
I-AOUT8 module is connected on IGS-NT or ID CAN1 (peripheral) bus. The corresponding module Address 1 to
4 (default 1) must be set on module (by Adr.1 and Adr.2 jumpers) and in controller configuration. Communication
fail is indicated in controller Alarm list and by binary output. Use DriveConfig PC tool for controller configuration.
It is possible to connect up to four I-AOUT8 units to one controller. CAN1 terminating 120Ω resistor jumper is
connected as default. AGND terminals are on the same potential.
General Description
I-AOUT8 is an extension unit with 8 Analog outputs. Each analog output can be switched by jumper for.
0 to 20 mA
0 to 10 VDC
PWM (Pulse With Modulation on 1,2 kHz)
I-AOUT8 modules is connected on CAN 1 (peripheral) bus. The corresponding module Address 1 to 4 (default 1)
must be set on module (by Adr.1 and Adr.2 jumpers) and in controller configuration. Communication fail is
indicated in controller Alarm list and by binary output. Use DriveConfig PC tool for controller configuration.
It is possible to connect up to four I-AOUT8 units to one controller.
I-AOUT8 unit can be mounted on DIN rail (35 mm).
CAN 1 terminating 120 Ω resistor jumper is connected in default. AGND terminals are on the same potential.
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...