InteliDrive DCU Industrial 3.4.0 Global Guide
291
Measuring voltage
Ranges: ±1 V, 0 – 2,5 V, 0 – 5 V, 0 – 10 V
Impulse input
1 channel
Can be configured as
Impulse
Impulse/time
RPM
All inputs can be configured to any logical function or protection.
It is possible to connect up to 10 modules to the InteliGen-NT, InteliSys-NT or InteliMains-NT controllers or up
to 4 modules to the ID-DCU.
Inteli AIN8 module is connected to controller CAN1 bus.
Technical data
Dimension (W × H × D)
110 × 110 × 46 mm (4,3” × 4,3” × 1,8”)
Weight
221.5 grams
Interface to controller
CAN1
Analog inputs (not electric separated)
8 channels
*Voltage
Range
0-10 V
Accuracy
± 0,25 % of actual value + ± 25 mV
Current
Range
±20 mA
Accuracy
± 0.25 % of actual value + ± 50 µA
Resistance
Range
0- 10 kΩ
Accuracy
± 0.5 % of actual value + ± 2 Ω
Resistance
Pt100, Pt1000, Ni100, Ni1000 ± 2,5 °C
Impulse input
*RPM
Level of signal
2 Vpk-pk ÷ 70 Vpk-pk
Frequency range
4 Hz ÷ 10 kHz
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...