8. Configure binary Input SW: PLC values: PLC Bout 1.1.
9. Rename output to RPM out
10. Go to I/O window and configure analog SCM AOUT1 as RPM out. Then configure output convert Low limit
(0 RPM ~ 0.00V output) and High output convert limit (2000 RPM ~ 10.00V output).