InteliDrive DCU Industrial 3.4.0 Global Guide
179
Related FW
3.4.0
Related applications
AS, SS
Comm object
165
Description
is decreased / increased when the binary input is closed. Speed Down has
higher priority when both Up and Down inputs are active. RPM inc/dec rate is defined by
Engine speed can be set by Logical Analog Input Requested RPM or by
and
Following Speed Request initialization is valid when
is not configured.
Speed Request (Idle) = 0.0 %. Inputs are active in LOC (Local) mode.
Speed Request (Running) = 50.0 % for AUX (ECU 50 % = Nominal RPM).
Speed Request (Running) = 0.0 % for PRP.
See Engine Values:
and
modes.
The Binary inputs SpeedUp and SpeedDown ramp
function is for the 0.6 sec constant 0.4 %/s and does not
depend on
setting. This
function enables fine setting of Engine speed to specific
like 1500 RPM value.
Dual rate ramp
Note:
Minimal Speed Up and Speed Down pulse duration is 110 ms to be accepted by controller.
Speed Up
Related FW
3.4.0
Related applications
AS, SS
Comm object
166
Description
Binary input for ECU Alarm acknowledge (level sensitive) has the same function as controller front panel
Fault reset
button (screen sensitive - active only in ECU Alarm list screen).
Note:
Activation of ECU Fault reset will affect InteliDrive DCU Industrial controller only, no reset
request is sent to ECU. There is separated acknowledge input for Alarms – see Binary input
ECU FltReset
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...