Table 931: DSTPDIS Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
EF Cur stabilization 0=False
1=True
0=False
EF current stabili-
zation enabled
Fact EF current Bal 1.000...2.000
0.001
1.200
Residual current ra-
tio for parallel line
compensation
Zone timer mode
1=Independent
2=Common
1=Independent
Operate timer start
mode, zones
Voltage Mem time
0...300000
ms
10
40
Voltage memory
time
4.7.1.10
DSTPDIS Monitored data
Table 932: DSTPDIS Monitored data
Name
Type
Values (Range)
Unit
Description
STARTS_GFC
Enum
4=AB Fault
5=BC Fault
6=CA Fault
7=ABC Fault
-5=No fault
1=AG Fault
2=BG Fault
3=CG Fault
Start signals for phases
A, B and C, GFC
RELEASE_PE
Enum
-5=No fault
1=AG Fault
2=BG Fault
3=CG Fault
4=AB Fault
5=BC Fault
6=CA Fault
7=ABC Fault
Release signals for PE-
loops, GFC
RELEASE_PP
Enum
5=BC Fault
6=CA Fault
7=ABC Fault
4=AB Fault
-5=No fault
Release signals for
PP/3P loops, GFC
EARTH_FLT
BOOLEAN
0=False
1=True
Indication of a single
phase earth-fault, GFC
DIR_E_FLT
Enum
0=unknown
1=forward
2=backward
3=both
Earth-fault direction
(low imp. earthed), GFC
STARTS_Z1
INT32
-5...63
Start signals for phases
A, B and C, zone 1
STARTS_Z2
INT32
-5...63
Start signals for phases
A, B and C, zone 2
STARTS_Z3
INT32
-5...63
Start signals for phases
A, B and C, zone 3
Table continues on the next page