Table 404: DPHLPDOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Num of start pha-
ses
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases
required for oper-
ate activation
Curve parameter A 0.0086...120.0000
0.0001
28.2000
Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120
0.0001
0.1217
Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00
0.01
2.00
Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00
0.01
29.10
Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0
0.1
1.0
Parameter E for
customer program-
mable curve
Table 405: DPHLPDOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Minimum operate
time
20...60000
ms
1
20
Minimum operate
time for IDMT
curves
Reset delay time
0...60000
ms
1
20
Reset delay time
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used meas-
urement mode
Allow Non Dir
0=False
1=True
0=False
Allows prot activa-
tion as non-dir
when dir info is in-
valid
Min operate current 0.01...1.00
xIn
0.01
0.01
Minimum operating
current
Min operate volt-
age
0.01...1.00
xUn
0.01
0.01
Minimum operating
voltage
DPHHPDOC Settings
Table 406: DPHHPDOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.10...40.00
xIn
0.01
0.10
Start value
Start value Mult
0.8...10.0
0.1
1.0
Multiplier for scal-
ing the start value
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Time multiplier
0.025...15.000
0.005
1.000
Time multiplier
in IEC/ANSI IDMT
curves
Operating curve
type
1=ANSI Ext. inv.
15=IEC Def. Time
Selection of time
delay curve type
Table continues on the next page
Protection functions
1MRS759142 F
364