Table 376: PHLPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Minimum operate
time
20...60000
ms
1
20
Minimum operate
time for IDMT
curves
Reset delay time
0...60000
ms
1
20
Reset delay time
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
5=Wide P-to-P
2=DFT
Selects used meas-
urement mode
PHHPTOC Settings
Table 377: PHHPTOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.10...40.00
xIn
0.01
0.10
Start value
Start value Mult
0.8...10.0
0.1
1.0
Multiplier for scal-
ing the start value
Time multiplier
0.025...15.000
0.005
1.000
Time multiplier
in IEC/ANSI IDMT
curves
Operate delay time 40...300000
ms
10
40
Operate delay time
Operating curve
type
1=ANSI Ext. inv.
3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
17=Programmable
15=IEC Def. Time
Selection of time
delay curve type
Table 378: PHHPTOC Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate
Selection of reset
curve type
Table 379: PHHPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Num of start pha-
ses
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases
required for oper-
ate activation
Curve parameter A 0.0086...120.0000
0.0001
28.2000
Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120
0.0001
0.1217
Parameter B for
customer program-
mable curve
Table continues on the next page