5.11.6.1
RESCPSCH Input signals
Table 1191: RESCPSCH Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
BLK_CS_OPR
BOOLEAN
0=False
Signal for blocking
CS and OPR in all
schemes
CSBLK
BOOLEAN
0=False
Reverse residual over-
current signal for Car-
rier Send
CACC
BOOLEAN
0=False
Signal to be used for
tripping by Communi-
cation Scheme
CSOR
BOOLEAN
0=False
Overreaching residual
overcurrent signal for
Carrier Send
CSUR
BOOLEAN
0=False
Underreaching resid-
ual overcurrent signal
for Carrier Send
CR_PRM
BOOLEAN
0=False
Received teleprotec-
tion permissive from
the other side
CR_BLOCKING
BOOLEAN
0=False
Received teleprotec-
tion blocking from
the other side
CR_INTER_TR
BOOLEAN
0=False
Received direct trip
from the other side
CRG
BOOLEAN
0=False
Carrier guard signal
received
5.11.6.2
RESCPSCH Output signals
Table 1192: RESCPSCH Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
CS_PRM
BOOLEAN
Permissive transmitted to the
other side
CS_BLOCKING
BOOLEAN
Blocking transmitted to the
other side
CS_INTER_TR
BOOLEAN
Direct trip transmitted to the
other side
Table continues on the next page
1MRS759142 F
Protection related functions
REX640
Technical Manual
1263