
Parameter
Values (Range)
Unit
Step
Default
Description
Opening time of
CB1
0...200
ms
1
40
Opening time of
the breaker feeder1
Opening time of
CB2
0...200
ms
1
40
Opening time of
the breaker feeder2
Close cmd delay
time
0...200
ms
1
0
Breaker close com-
mand delay time
Load shedding
mode
1=None
2=Instantaneous
3=Voltage based
4=Time based
1=None
Load shedding op-
eration mode
Enable decoupling
1=Off
2=Transfer based
3=CB man close
4=Both
1=Off
Enable circuit
breaker decoupling
Decoupling delay
50...200000
ms
1
1000
Circuit breaker de-
coupling delay
9.12.9
HSABTC Monitored data
Table 1614: HSABTC Monitored data
Name
Type
Values (Range)
Unit
Description
STATUS
Enum
0=Off
1=Ready - sync
2=Ready - no sync
3=Not ready - sync
4=Not ready - no sync
5=Transfer running
6=Not defined
Transfer status
FRQ_DIFF
FLOAT32
-30.00...30.00
Hz
Frequency difference
between standby feed-
er and busbar
ANG_DIFF_1
FLOAT32
-180.0...180.0
deg
Angle difference be-
tween feeder 1 and bus-
bar
ANG_DIFF_2
FLOAT32
-180.0...180.0
deg
Angle difference be-
tween feeder 2 and bus-
bar
CLS_T_CB1
FLOAT32
0.0...10000.0
ms
Measured close time for
circuit breaker of feeder
1
CLS_T_CB2
FLOAT32
0.0...10000.0
ms
Measured close time for
circuit breaker of feeder
2
OPN_T_CB1
FLOAT32
0.0...10000.0
ms
Measured open time for
circuit breaker of feeder
1
OPN_T_CB2
FLOAT32
0.0...10000.0
ms
Measured open time for
circuit breaker of feeder
2
ACT_CLS_T_CB1
FLOAT32
0.0...10000.0
ms
Active close time for
circuit breaker of feeder
1
ACT_CLS_T_CB2
FLOAT32
0.0...10000.0
ms
Active close time for
circuit breaker of feeder
2
Table continues on the next page
1MRS759142 F
Control functions
REX640
Technical Manual
1803