Table 1511: SECRSYN Monitored data
Name
Type
Values (Range)
Unit
Description
ENERG_STATE
Enum
0=Unknown
1=Both Live
2=Live L, Dead B
3=Dead L, Live B
4=Both Dead
Energization state of
Line and Bus
U_DIFF_MEAS
FLOAT32
-3.00...3.00
xUn
Calculated voltage am-
plitude difference
FR_DIFF_MEAS
FLOAT32
-1.500...1.500
xFn
Calculated voltage fre-
quency difference
PH_DIFF_MEAS
FLOAT32
-180.00...180.00
deg
Calculated voltage
phase angle difference
U_DIFF_SYNC
BOOLEAN
0=False
1=True
Voltage difference out
of limit for synchroniz-
ing
PH_DIF_SYNC
BOOLEAN
0=False
1=True
Phase angle difference
out of limit for synchro-
nizing
FR_DIFF_SYNC
BOOLEAN
0=False
1=True
Frequency difference
out of limit for synchro-
nizing
SECRSYN
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
9.5.10
Technical data
Table 1512: SECRSYN Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the voltage
measured: f
n
±1 Hz
Voltage:
±3.0 % of the set value or ±0.01 × U
n
Frequency:
±10 mHz
Phase angle:
±3°
Reset time
<50 ms
Reset ratio
Typically 0.96
Operate time accuracy in definite time mode ±1.0 % of the set value or ±20 ms
Control functions
1MRS759142 F
1556
REX640
Technical Manual