Parameter
Values (Range)
Unit
Step
Default
Description
19=RD type
Operate delay time 40...200000
ms
10
5000
Operate delay time
Alarm delay time
40...200000
ms
10
200000
Alarm delay time
Table 1082: HCUBPTOC Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Natural Comp Ena
PhA
0=False
1=True
0=False
Enable natural un-
balance compensa-
tion PhA
Natural Comp Ena
PhB
0=False
1=True
0=False
Enable natural un-
balance compensa-
tion PhB
Natural Comp Ena
PhC
0=False
1=True
0=False
Enable natural un-
balance compensa-
tion PhC
Table 1083: HCUBPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Curve parameter A 0.00860...120.0000
0
0.00001
28.20000
Parameter A for
customer program-
mable curve
Curve parameter B 0.00000...0.71200
0.00001
0.12170
Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00
0.01
2.00
Parameter C for
customer program-
mable curve
Curve parameter E 0.0...1.0
0.1
1.0
Parameter E for
customer program-
mable curve
Table 1084: HCUBPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
Minimum operate
time
20...60000
ms
1
20
Minimum operate
time for IDMT
curves
4.12.3.9
HCUBPTOC Monitored data
Table 1085: HCUBPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
I_NAT_AMPL_A
FLOAT32
0.00...5.00
xIn
Recorded natural unbal-
ance current amplitude
phase A
I_NAT_ANGL_A
FLOAT32
-179.00...179.00
deg
Recorded natural un-
balance current angle
phase A
I_NAT_AMPL_B
FLOAT32
0.00...5.00
xIn
Recorded natural unbal-
ance current amplitude
phase B
Table continues on the next page
Protection functions
1MRS759142 F
1140
REX640
Technical Manual