Fault indication
Fault
code
Additional
information
Fast self-
recovery
attempt
Slow 10min
self-
recovery
(# of
attempts)
Immediate
IRF-mode
Action in permanent fault
state
Internal Fault
PO-relay(s), Slot
F
-25
Runtime error:
Faulty Power Out-
put relay(s) in card
located in slot F.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot F.
Internal Fault
PO-relay(s), Slot
G
-26
Runtime error:
Faulty Power Out-
put relay(s) in card
located in slot G.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot G.
Internal Fault
PO-relay(s), Slot
A1
-27
Runtime error:
Faulty Power Out-
put relay(s) in card
located in slot A1.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot A1.
Internal Fault
Conf. error, Slot
C
-30
Start up error: Card
in slot C is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No
No
Yes
Check that the card in slot
C is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot C.
Internal Fault
Conf. error, Slot
E
-31
Start up error: Card
in slot E is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No
No
Yes
Check that the card in slot
E is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot E.
Internal Fault
Conf. error, Slot
A2
-32
Start up error: Card
in slot A2 is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No
No
Yes
Check that the communica-
tion card in slot A2 is prop-
er type and properly instal-
led. Then restart the relay.
If does not then recover by
restarting, it is hardware
module failure most likely
in question. Exchange the
communication module in
slot A2.
Internal Fault
Conf. error, Slot
B
-33
Start up error: Card
in slot B is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No
No
Yes
Check that the card in slot
B is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot B.
Internal Fault
Conf. error, Slot
D
-34
Start up error: Card
in slot D is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No
No
Yes
Check that the card in slot
D is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
Table continues on the next page
1MRS759142 F
Basic functions
REX640
Technical Manual
105