Table 1262: HZCCBSPVC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Start value
1.0...100.0
%In
0.1
10.0
Start value, per-
centage of the
nominal current
Alarm delay time
100...300000
ms
10
3000
Alarm delay time
Alarm output mode 1=Non-latched
3=Lockout
3=Lockout
Select the opera-
tion mode for
alarm output
Table 1263: HZCCBSPVC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
10
20
Reset delay time
Measurement
mode
2=DFT
3=Peak-to-Peak
2=DFT
Selects used meas-
urement mode
6.3.9.3
HZCCCSPVC Settings
Table 1264: HZCCCSPVC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Start value
1.0...100.0
%In
0.1
10.0
Start value, per-
centage of the
nominal current
Alarm delay time
100...300000
ms
10
3000
Alarm delay time
Alarm output mode 1=Non-latched
3=Lockout
3=Lockout
Select the opera-
tion mode for
alarm output
Table 1265: HZCCCSPVC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
10
20
Reset delay time
Measurement
mode
2=DFT
3=Peak-to-Peak
2=DFT
Selects used meas-
urement mode
6.3.10
Monitored data
6.3.10.1
HZCCASPVC Monitored data
Table 1266: HZCCASPVC Monitored data
Name
Type
Values (Range)
Unit
Description
HZCCASPVC
Enum
1=on
2=blocked
3=test
4=test/blocked
Status
1MRS759142 F
Supervision functions
REX640