
Table 1114: Retrip logic operation
Value of setting CB
fail retrip mode
Value of setting CB
failure mode
Retrip functionality
Off
Current
Breaker status
Both(AND)
Both(OR
Retrip functionality switched off.
TRRET
is
not activated.
Without Check
Current
Breaker status
Both(AND)
Both(OR
TRRET
is activated after Timer 1 elapses.
Current check
Current
TRRET
is activated after Timer 1 elapses and
any phase current exceeds
Current value
set-
ting.
Breaker status
TRRET
is activated after Timer 1 elapses and
CB is in closed position.
Both(AND)
TRRET
is activated after Timer 1 elapses and
CB is in closed position and any phase cur-
rent exceeds
Current value
setting.
Both(OR)
TRRET
is activated after Timer 1 elapses and
either of the following is true:
• CB is in closed position.
• Any phase current exceeds
Current value
setting.
TRRET
activation is blocked if either
CB_FAULT_AL
output (from Timer 3)
is active or the
BLOCK
input is activated.
Once activated,
TRRET
remains active for the set
Trip pulse time or until the reasons
for activation are reset.
TRRET
is also reset if
CB_FAULT_AL
or
BLOCK
is activated.
Protection related functions
1MRS759142 F
1168
REX640
Technical Manual