
Name
Type
Values (Range)
Unit
Description
I0_HIGH_WARN
BOOLEAN
0=False
1=True
Zero sequence high
warning
I2_INST
FLOAT32
0.00...40.00
xIn
Negative sequence cur-
rent amplitude, instan-
taneous value
I2_ANGL
FLOAT32
-180.00...180.00
deg
Negative sequence cur-
rent angle
I2_DB
FLOAT32
0.00...40.00
xIn
Negative sequence cur-
rent amplitude, dead-
band value
I2_RANGE
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Negative sequence cur-
rent amplitude range
I1_INST
FLOAT32
0.00...40.00
xIn
Positive sequence cur-
rent amplitude, instan-
taneous value
I1_ANGL
FLOAT32
-180.00...180.00
deg
Positive sequence cur-
rent angle
I1_DB
FLOAT32
0.00...40.00
xIn
Positive sequence cur-
rent amplitude, dead-
band value
I1_RANGE
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Positive sequence cur-
rent amplitude range
I0_INST
FLOAT32
0.00...40.00
xIn
Zero sequence current
amplitude, instantane-
ous value
I0_ANGL
FLOAT32
-180.00...180.00
deg
Zero sequence current
angle
I0_DB
FLOAT32
0.00...40.00
xIn
Zero sequence current
amplitude, deadband
value
I0_RANGE
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Zero sequence current
amplitude range
8.1.11.8
Technical data
Table 1420: CSMSQI Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f/f
n
= ±2 Hz
±1.0 % or ±0.002 × I
n
at currents in the range of 0.01...4.00 × I
n
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1MRS759142 F
Measurement functions
REX640
Technical Manual
1475