4.1.5.9
T1PTTR Monitored data
Table 440: T1PTTR Monitored data
Name
Type
Values (Range)
Unit
Description
TEMP
FLOAT32
-100.0...9999.9
°C
The calculated temper-
ature of the protected
object
TEMP_RL
FLOAT32
0.00...99.99
The calculated temper-
ature of the protected
object relative to the
operate level
T_OPERATE
INT32
0...60000
s
Estimated time to oper-
ate
T_ENA_CLOSE
INT32
0...60000
s
Estimated time to deac-
tivate BLK_CLOSE
TEMP_AMB
FLOAT32
-99...999
°C
The ambient tempera-
ture used in the calcula-
tion
T1PTTR
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.1.5.10
Technical data
Table 441: T1PTTR Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
Current measurement: ±1.5% of the set value
or ±0.002 × I
n
(at currents in the range of
0.01...4.00 × I
n
)
Operate time accuracy
1
±2.0% of the theoretical value or ±0.50 s
4.1.6
Three-phase thermal overload protection, two time
constants T2PTTR (ANSI 49T/G/C)
4.1.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase thermal overload pro-
tection, two time constants
T2PTTR
3Ith>T/G/C
49T/G/C
1
Overload current > 1.2 × Operate level temperature
1MRS759142 F
Protection functions
REX640
Technical Manual
389