
UTVTR Output signals
Table 130: UTVTR Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm
WARNING
BOOLEAN
Warning
URES_ALARM
BOOLEAN
Alarm
URES_WARNING
BOOLEAN
Warning
U3P
SIGNAL
Three-phase voltages
URES_CLC
SIGNAL
Residual voltage, calculated
URES_MEAS
SIGNAL
Residual voltage, measured
URES_CLC_DR
SIGNAL
Residual voltage, calculated,
for disturbance recorder
URES_MEAS_DR
SIGNAL
Residual voltage, measured,
for disturbance recorder
U1_DR
SIGNAL
Phase voltage U1 for disturb-
ance recorder
U2_DR
SIGNAL
Phase voltage U2 for disturb-
ance recorder
U3_DR
SIGNAL
Phase voltage U3 for disturb-
ance recorder
NPS_DR
SIGNAL
Negative sequence current
for disturbance recorder
PPS_DR
SIGNAL
Positive sequence current for
disturbance recorder
FREQ_DR
SIGNAL
Measured frequency for dis-
turbance recorder
3.17.3.6
UTVTR Settings
Table 131: UTVTR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Voltage input type
1=Voltage trafo
3=Voltage sensor
1=Voltage trafo
Type of the voltage
input
Primary voltage
0.100...800.000
kV
0.001
20.000
Primary rated
phase-to-phase
voltage
Secondary voltage
57...416
V
1
100
Secondary rated
phase-to-phase
voltage
Division ratio
1000...20000
1
10000
Voltage sensor divi-
sion ratio
VT connection
1=Wye
2=Delta
2=Delta
Voltage transducer
measurement con-
nection
Amplitude Corr A
0.9000...1.1000
0.0001
1.0000
Phase A Voltage
phasor magnitude
Table continues on the next page
1MRS759142 F
Basic functions
REX640
Technical Manual
201