4.5.6.9
PSPTUV Monitored data
Table 838: PSPTUV Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
PSPTUV
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.5.6.10
Technical data
Table 839: PSPTUV Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured voltage:
f
n
±2 Hz
±1.5% of the set value or ±0.002 × U
n
Start time
1, 2
U
Fault
= 0.99 × set
Start value
U
Fault
= 0.9 × set
Start value
Minimum
Typical
Maximum
52 ms
44 ms
55 ms
47 ms
58 ms
50 ms
Reset time
Typically 40 ms
Reset ratio
Depends on the set
Relative hysteresis
Retardation time
<35 ms
Operate time accuracy in definite
time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
4.5.7
Overexcitation protection OEPVPH (ANSI 24)
4.5.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Overexcitation protection
OEPVPH
U/f>
24
1
Start value = 1.0 × U
n
, positive-sequence voltage before fault = 1.1 × U
n
, f
n
= 50 Hz, positive
sequence undervoltage with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
2
Includes the delay of the signal output contact
Protection functions
1MRS759142 F
884
REX640
Technical Manual