Name
Type
Default
Description
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
RCA_CTL
BOOLEAN
0=False
Relay characteristic
angle control
5.15.7.2
DNZSRDIR Output signals
Table 1224: DNZSRDIR Output signals
Name
Type
Description
RELEASE
BOOLEAN
Release signal if direction cri-
teria is satisified
DIRECTION
Enum
Direction information
5.15.8
DNZSRDIR Settings
Table 1225: DNZSRDIR Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Release delay time
0...1000
ms
10
10
Release delay time
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Characteristic an-
gle
-179...180
deg
1
60
Characteristic an-
gle
Max forward angle
0...180
deg
1
88
Maximum phase
angle in forward di-
rection
Min forward angle
0...180
deg
1
88
Minimum phase an-
gle in forward di-
rection
Max reverse angle
0...180
deg
1
88
Maximum phase
angle in reverse di-
rection
Min reverse angle
0...180
deg
1
88
Minimum phase an-
gle in reverse direc-
tion
Table 1226: DNZSRDIR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Pol quantity
3=Zero seq. volt.
4=Neg. seq. volt.
3=Zero seq. volt.
Reference quantity
used to determine
fault direction
1MRS759142 F
Protection related functions
REX640
Technical Manual
1293