Parameter
Values (Range)
Unit
Step
Default
Description
Max forward angle
0...90
deg
1
88
Maximum phase
angle in forward di-
rection
Max reverse angle
0...90
deg
1
88
Maximum phase
angle in reverse di-
rection
Min forward angle
0...90
deg
1
88
Minimum phase an-
gle in forward di-
rection
Min reverse angle
0...90
deg
1
88
Minimum phase an-
gle in reverse direc-
tion
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Table 1216: DPSRDIR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 1217: DPSRDIR Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
Min operate current 0.01...1.00
xIn
0.01
0.10
Minimum operating
current
Min operate volt-
age
0.01...1.00
xUn
0.01
0.30
Minimum operating
voltage
5.14.9
DPSRDIR Monitored data
Table 1218: DPSRDIR Monitored data
Name
Type
Values (Range)
Unit
Description
ANGLE_RCA
FLOAT32
-180.00...180.00
deg
Angle between operat-
ing angle and charac-
teristic angle
DPSRDIR
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
5.15
Neutral power directional element DNZSRDIR (ANSI
67N-TC)
1MRS759142 F
Protection related functions
REX640
Technical Manual
1285