
Module
Description
COM1005
1 × RJ-45 (LHMI port) + 2 × LC + 1 × LD-SFP + 1 × RS-485/IRIG-B + 1 × FO
UART
BIO1001/
BIO1003
14 × BI + 8 × SO
BIO1002/
BIO1004
6 × SPO + 2 × SPO (TCS) + 9 × BI
RTD1001
10 × RTD ch 2 × mA channels (input/output)
RTD1002
3 × RTD ch 6 × mA channels (input/output) + 12 x BI
AIM1001
4 × CT + 1 × CT (sensitive, for residual current only) + 5 × VT
AIM1002
6 × CT + 4 × VT
SIM1901
3 × combi sensor inputs (RJ-45) + 1 × CT (sensitive, for residual current
only) + 1 × VT
SIM1902
3 × combi sensor inputs (RJ-45) + 1 × CT (sensitive, for residual current
only) + 1 × VT
PSM1001
24...60 VDC, 3 × PO (TCS) + 2 × PO + 3 × SO + 2 × SSO
PSM1002
48...250 VDC / 100...240 VAC, 3 × PO (TCS) + 2 × PO + 3 × SO + 2 × SSO
PSM1003
110/125 VDC (77...150 VDC), 3 × PO (TCS) + 2 × PO + 3 × SO + 2 × SSO
PO = Power Output
SO = Signal Output
SPO = Static Power Output
SSO = Static Signal Output
The relay has a nonvolatile memory which does not need any periodical
maintenance. The nonvolatile memory stores all events, recordings and logs to a
memory which retains data if the relay loses its auxiliary supply.
2.3
Local HMI
The LHMI is used for setting, monitoring and controlling the protection relay and
the related process. It comprises a 7-inch color screen with capacitive touch sensing
and a Home button at the bottom of the LHMI.
The LHMI must be paired with the protection relay to enable all the
functionalities in it. See the operation manual for the pairing procedure.
The LHMI is an accessory for the relay which is fully operational even
without the LHMI.
1MRS759142 F
REX640 overview
REX640
Technical Manual
45