Parameter
Values (Range)
Unit
Step
Default
Description
2=DFT
3=Peak-to-Peak
Min operate current 0.5...100.0
%In
0.1
0.5
Minimum operating
current
Min operate volt-
age
1.0...100.0
%Un
0.1
1.0
Minimum operating
voltage
Correction angle
0.0...10.0
deg
0.1
0.0
Characteristic cor-
rection angle in
IoCos and IoSin
mode
Pol reversal
0=False
1=True
0=False
Rotate polarizing
quantity
Pol quantity
3=Zero seq. volt.
4=Neg. seq. volt.
3=Zero seq. volt.
Reference quantity
used to determine
fault direction
DEFHPDEF Settings
Table 547: DEFHPDEF Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.10...40.00
xIn
0.01
0.10
Start value
Start value Mult
0.8...10.0
0.1
1.0
Multiplier for scal-
ing the start value
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Time multiplier
0.025...15.000
0.005
1.000
Time multiplier
in IEC/ANSI IDMT
curves
Operating curve
type
1=ANSI Ext. inv.
3=ANSI Norm. inv.
5=ANSI Def. Time
15=IEC Def. Time
17=Programmable
15=IEC Def. Time
Selection of time
delay curve type
Operate delay time 40...300000
ms
10
40
Operate delay time
Characteristic an-
gle
-179...180
deg
1
-90
Characteristic an-
gle
Max forward angle
0...180
deg
1
80
Maximum phase
angle in forward di-
rection
Max reverse angle
0...180
deg
1
80
Maximum phase
angle in reverse di-
rection
Min forward angle
0...180
deg
1
80
Minimum phase an-
gle in forward di-
rection
Min reverse angle
0...180
deg
1
80
Minimum phase an-
gle in reverse direc-
tion
Voltage start value 0.010...1.000
xUn
0.001
0.010
Voltage start value
Table 548: DEFHPDEF Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Type of reset curve 1=Immediate
1=Immediate
Selection of reset
curve type
Table continues on the next page
Protection functions
1MRS759142 F
478
REX640
Technical Manual