Parameter
Values (Range)
Unit
Step
Default
Description
Voltage level 9
0.00...1.20
xUn
0.01
0.90
9th voltage coordi-
nate for defining
LVRT curve
Voltage level 10
0.00...1.20
xUn
0.01
0.90
10th voltage coor-
dinate for defining
LVRT curve
Recovery time 1
0...300000
ms
1
500
1st time coordinate
for defining LVRT
curve
Recovery time 2
0...300000
ms
1
1000
2nd time coordi-
nate for defining
LVRT curve
Recovery time 3
0...300000
ms
1
10000
3rd time coordinate
for defining LVRT
curve
Recovery time 4
0...300000
ms
1
10000
4th time coordi-
nate for defining
LVRT curve
Recovery time 5
0...300000
ms
1
10000
5th time coordinate
for defining LVRT
curve
Recovery time 6
0...300000
ms
1
10000
6th time coordinate
for defining LVRT
curve
Recovery time 7
0...300000
ms
1
10000
7th time coordinate
for defining LVRT
curve
Recovery time 8
0...300000
ms
1
10000
8th time coordinate
for defining LVRT
curve
Recovery time 9
0...300000
ms
1
10000
9th time coordinate
for defining LVRT
curve
Recovery time 10
0...300000
ms
1
10000
10th time coordi-
nate for defining
LVRT curve
4.5.8.9
LVRTPTUV Monitored data
Table 858: LVRTPTUV Monitored data
Name
Type
Values (Range)
Unit
Description
LVRTPTUV
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.5.8.10
Technical data
Table 859: LVRTPTUV Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
voltage:
f
n
±2 Hz
±1.5% of the set value or ±0.002 × U
n
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
907