impedance defined by the
Ris Fwd Rch Lod GFC, Ris Rv Rch Lod GFC and Angle load
area GFC settings.
The underimpedance characteristics in case of phase-to-earth measuring elements
are illustrated in
. Similar characteristics apply also to
phase-to-phase measuring elements with independent settings.
R
X
X Gnd Fwd reach GFC
X Gnd Rv reach GFC
R
X
Angle load area GFC
Ris Fwd Rch Load GFC
Fault detected
Fault detected
Angle load area GFC
Ris Rv Rch Load GFC
Figure 529: Circular mho underimpedance characteristics
R
X
X Gnd Fwd reach GFC
X Gnd Rv reach GFC
R
X
Angle load area GFC
Ris Fwd Rch load GFC
Fault detected
Fault detected
Angle load area GFC
Ris Gnd Fwd Rch GFC
Ris Gnd Rv Rch GFC
Ris Rv Rch load GFC
Figure 530: Quadrilateral underimpedance characteristics
Table 914: Conversion from element start to monitored data signals
Start of element
START_GFC STARTS_GF
C
RELEASE_P
E
RELEASE_P
P
Z
A
< &
EARTH_FLT
TRUE
AG Fault
AG Fault
No fault
Z
B
< &
EARTH_FLT
TRUE
BG Fault
BG Fault
No fault
Z
C
< &
EARTH_FLT
TRUE
CG Fault
CG Fault
No fault
Z
AB
<
TRUE
AB Fault
No fault
AB Fault
Z
BC
<
TRUE
BC Fault
No fault
BC Fault
Z
CA
<
TRUE
CA Fault
No fault
CA Fault
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
955