7.2.6.2
ESDCSSWI Output signals
Table 1317: ESDCSSWI Output signals
Name
Type
Description
TRV_T_OP_ALM
BOOLEAN
Switch open travel time ex-
ceeded set value
TRV_T_CL_ALM
BOOLEAN
Switch close travel time ex-
ceeded set value
OPR_ALM
BOOLEAN
Number of switch operations
exceeds alarm limit
OPR_LO
BOOLEAN
Number of switch operations
exceeds lockout limit
MON_ALM
BOOLEAN
Switch not operated for long
time alarm
OPENPOS
BOOLEAN
Apparatus open position
INVALIDPOS
BOOLEAN
Apparatus position is invalid
CLOSEPOS
BOOLEAN
Apparatus closed position
7.2.7
ESDCSSWI Settings
Table 1318: ESDCSSWI Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Open alarm time
40...30000
ms
10
15000
Alarm level setting
for open travel time
in ms
Close alarm time
40...30000
ms
10
15000
Alarm level setting
for close travel time
in ms
Alarm Op number
0...99999
1
200
Alarm limit for
number of opera-
tions
Inactive Alm days
0...9999
1
2000
Alarm limit value of
the inactive days
counter
Travel time Clc
mode
1=From Cmd to Pos
2=From Pos to Pos
2=From Pos to Pos Travel time mode
selection
Lockout Op num-
ber
0...99999
1
300
Lock out limit for
number of opera-
tions