Parameter
Values (Range)
Unit
Step
Default
Description
tection (Phase-to-
phase value of volt-
age)
Operate delay time 20...300000
ms
10
40
Operate delay time
Arm delay time
40...300000
ms
10
5000
Time delay to arm
the function
Disarm delay time
40...300000
ms
10
500
Time delay to dis-
arm the function
Table 429: GAEPVOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 430: GAEPVOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
4.1.4.9
GAEPVOC Monitored data
Table 431: GAEPVOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
GAEPVOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.1.4.10
Technical data
Table 432: GAEPVOC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current and voltages: f
n
±2 Hz
Current: ±1.5% of the set value or ± 0.002 × I
n
Voltage: ±1.5% of the set value or ±0.002 × U
n
Start time
1,2
Typically 20 ms
Reset time
Typically 35 ms
Reset ratio
Typically 0.96
Table continues on the next page
1
Results based on statistical distribution of 1000 measurements.
2
Measured with static signal output (SSO).
Protection functions
1MRS759142 F
382
REX640
Technical Manual