RESTCTR Output signals
Table 124: RESTCTR Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm
WARNING
BOOLEAN
Warning
IRES_MEAS
SIGNAL
Residual current, measured
IRES_MEAS_DR
SIGNAL
Residual current, measured,
for disturbance recorder
3.17.2.5
Settings
RESTCTR Settings
Table 125: RESTCTR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Current input type
2=Current trafo
4=Current sensor
2=Current trafo
Type of the current
input
Primary current
1.0...15000.0
A
0.1
100.0
Primary current
Secondary current
1=0.2A
2=1A
3=5A
2=1A
Secondary current
Rated secondary
Val
1.000...150.000
mV/Hz
0.001
3.000
Rated Secondary
Value (RSV) ratio
Amplitude Corr
0.9000...1.1000
0.0001
1.0000
Amplitude correc-
tion
Angle correction
-8.0000...8.0000
deg
0.0001
0.0000
Angle correction
factor
Table 126: RESTCTR Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reverse polarity
0=False
1=True
0=False
Reverse the polari-
ty of the residual
CT
Frequency adaptivi-
ty
0=Disable
1=Enable
0=Disable
Frequency adaptivi-
ty selection
3.17.2.6
Monitored data
Monitored data is available in three locations.
• Monitoring > I/O status > Analog inputs
• Monitoring > IED status > SMV traffic
• Monitoring > IED status > SMV accuracy
Basic functions
1MRS759142 F
196
REX640
Technical Manual