
check. The input
ITL_BYPASS
can be used for bypassing
ENA_CLOSE
input, while the
SYNC_BYPASS
can be used for bypassing
SYNC_OK
input. However, the
BLK_CLOSE
input always blocks the
CLOSE_ENAD
output. The CB opening (OPEN_ENAD) logic is
the same as CB closing logic, except that
SYNC_OK
and
SYNC_BYPASS
are used only
in closing.
The CB opening (
OPEN_ENAD
) logic is the same as CB closing logic, except
that
SYNC_OK
is used only in closing. The
SYNC_ITL_BYP
input is used in both
CLOSE_ENAD
and
OPEN_ENAD
logics.
AND
OR
OR
AND
ENA_CLOSE
ITL_BYPASS
SYNC_OK
BLK_CLOSE
CLOSE_ENAD
ENA_OPEN
ITL_BYPASS
OPEN_ENAD
BLK_OPEN
SYNC_BYPASS
OR
AND
Figure 824: Enabling and blocking logic for CLOSE_ENAD and OPEN_ENAD signals
Disconnector control DCXSWI and earthing switch control ESXSWI
Normally, the switch closing is enabled (that is, the
CLOSE_ENAD
signal is TRUE) by
activating the
ENA_CLOSE
input. The input
ITL_BYPASS
can be used for bypassing
this control. The
ITL_BYPASS
input can be used to activate the
CLOSE_ENAD
discarding the
ENA_CLOSE
input state. However, the
BLK_CLOSE
input always blocks
the
CLOSE_ENAD
output.
The CB opening (
OPEN_ENAD
) logic is identical to CB closing logic. The
ITL_BYPASS
input is used in both
CLOSE_ENAD
and
OPEN_ENAD
logics.
1MRS759142 F
Control functions
REX640
Technical Manual
1507